Heat Exchanger Failures





Heat exchangers usually provide a long service life with little or no maintenance because they do not contain any moving parts. However, there are four types of heat exchanger failures that can occur, and can usually be prevented: mechanical, chemically induced corrosion, a combination of mechanical and chemically induced corrosion, and scale, mud. and algae fouling. This article provides the plant engineer with a detailed look at the problems that can develop and describes the corrective actions that should be taken to prevent them. Mechanical-These failures can take seven different forms: metal erosion, steam or water hammer, vibration, thermal fatigue, freeze-up, thermal expansion. and loss of cooling water. Metal Erosion-Excessive fluid velocity on either the shell or tube side of the heat exchanger can cause damaging erosion as metal wears from the tubing. Any corrosion already present is accelerated as erosion removes the tube's protective films, exposing fresh metal to further attack. Most metal erosion problems occur inside the tubes. The U- bend of U-type heat exchangers and the tube entrances are the areas most prone to erosion. Figure 1 shows the metal loss in a U- bend caused by high-temperature water flashing to steam. Tube entrance areas experience severe metal loss when high-velocity fluid from a nozzle is divided into much smaller streams upon entering the heat exchanger. Stream dividing results in excessive turbulence with very high localized velocities. High velocity and turbulence produce a horseshoe erosion pattern at the tube entrance. 

Fig. 1. Metal erosion in U bend.


Maximum recommended velocity in the tubes and entrance nozzle is a function of many variables, including tube material, fluid handled, and temperature. Materials such as steel, stainless steel, and copper-nickel withstand higher tube velocities than copper. Copper is normally limited to 7.5 fps; the other materials can handle 10 or 11 fps. If water is flowing through copper tubing, the velocity should be less than 7.5 fps when it contains suspended solids or is softened. Erosion problems on the outside of tubes usually result from impingement of wet, high-velocity gases, such as steam. Wet gas impingement is controlled by oversizing inlet nozzles, or by placing impingement baffles in the inlet nozzle. Steam or Water, Hammer -- Pressure surges or shock waves caused by the sudden and rapid acceleration or deceleration of a liquid can cause steam or water hammer. The resulting pressure surges have been measured at levels up to 20,000 psi, which is high enough to rupture or collapse the tubing in a heat exchanger. For example, 3/4 in. x 20 BWG light drawn copper tubing has a burst pressure of 2100 psi and a collapse pressure of 600 psi. Damaging pressure surges can result from a cooling water flow interruption. The stagnant cooling water is heated enough to generate steam, and the resumption of the flow causes a sudden condensing of the steam and produces a damaging pressure surge, or water hammer. Cooling water flow should always be started before heat is applied to the exchanger. Fluid flow control valves that open or close suddenly also produce water hammer. Modulating control valves are preferable to on-off types.

 Fig. 2. Metal erosion at tube entrance


Vacuum breaker vents must be provided if condensables are handled in either the shell or tubes: they prevent steam hammer damage resulting from condensate accumulation. 


Fig. 3. Tube damage from steam

Figure 3 shows typical tube damage caused by steam hammer. In this case, condensate accumulated in the shell and rapidly accelerated. producing a high-pressure shock wave that collapsed the tube and caused the tear holes. Properly sized steam traps with return lines pitched to a condensate receiver or condensate return pump should be installed to prevent this type of damage. Vibration-Fxecssive vibration from equipment such as air compressors or refrigeration machines can cause tube failures in the form of a fatigue stress crack or erosion of tubing at the point of contact with baffles. Heat exchangers should be isolated from this type of vibration. Shell-side fluid velocities in excess of 4 fps can induce damaging vibrations in the tubes. causing a cutting action at support points with baffles.



Fig. 4. Velocity-induced vibration cut of tube.


 Fig. 4. Velocity-induced vibrations can also cause fatigue failures by work hardening the tubing at baffle contact points or in U-bend areas until a fatigue crack appears. Thermal Fatigue --Tubing, particularly in the U- bend area, can fail because of fatigue resulting from accumulated stresses associated with repeated thermal cycling. This problem is greatly aggravated as the temperature difference across the length of the U-bend tube increases.



Fig. 5. Thermal fatigue failure in U bend.


 Figure 5 shows an example of thermal fatigue. The temperature difference causes tube flexing, which produces a stress that acts additively until the tensile strength of the material is exceeded and it cracks. The crack usually runs radially around the tube, and many times results in a total break. In other cases, the crack occurs only halfway through the tube and then runs longitudinally along it. Freeze-Up -- These failures are most common in evaporators or condensers; however, they can occur in any heat exchanger in which temperatures drop below the freezing point of either fluid in the unit. Freeze-up results from failure to provide thermal protection, a malfunction of the thermal protection control system or protective heating device, improper drainage of the unit for winter shutdown, or inadequate concentration of antifreeze solutions. For example, assume a chiller has improper settings or malfunctioning controls that cool the water to a point below its freezing point. lce forms and exerts tremendous pressure in the tubing, which causes it to rupture or collapse. Collapse in an evaporator, 


Fig. 6. Collapse of evaporator tube because of freeze-up.

Fig. 6, usually occurs near the tube sheet where the tube is not protected by an inner splint. Freeze-up failure in a condenser tube is shown in Fig. 7.


Fig. 7. Rupture of condenser tube because of freeze up.

 In this case, cooling water was circulating inside the tube, refrigerant was condensed on the externally finned surface, and the unit was not properly drained for winter shutdown. The tube distortion indicates that it was exposed to excessive pressure caused by the freezing water. This type of failure is also caused by the sudden release of refrigerant pressure from the condenser. The sudden release caused by a line break or relief valve discharge suddenly drops the pressure below the boiling. point of the refrigerant. Boiling extracts heat from water in the tubes and the liquid freezes. Thermal Expansion-These failures are must common in steam heated exchangers; however, they can occur in any type in which fluid being heated is valved off without provisions to absorb thermal expansion. In steam-heated systems, cooling down or condensing residual steam in the shell after the steam control valve closes continues to heat water or other fluids on the tube side. Continued heating causes thermal expansion, which creates pressures far in excess of the strength of tube sheets, cast heads, and other heat exchanger components. Cast iron parts usually fracture because of lack of ductility: steel tube sheets become bowed or permanently distorted because the material's yield point is exceeded. Figure 8 shows thermal expansion failure of a cast iron heat exchanger head. 
Relief valves are installed in the heated fluid


Thermal Expansion-These failures are must common in steam heated exchangers; however, they can occur in any type in which fluid being heated is valved off without provisions to absorb thermal expansion. In steam-heated systems, cooling down or condensing residual steam in the shell after the steam control valve closes continues to heat water or other fluids on the tube side. Continued heating causes thermal expansion, which creates pressures far in excess of the strength of tube sheets, cast heads, and other heat exchanger components. 


Fig 8. Thermal expansion failure of cast iron head.

Cast iron parts usually fracture because of lack of ductility: steel tube sheets become bowed or permanently distorted because the material's yield point is exceeded. Figure 8 shows thermal expansion failure of a cast iron heat exchanger head.

Commenti

  1. Nice Information. Galaxy Industrial Equipment - Top Heat Exchanger Manufacturer In India, according to our international and domestic customer specifications. Our heat exchangers are made of high quality steel with high structural strength and long service life.

    For More Information Visit: http://www.galaxyprocess.in/heat-exchange.html

    RispondiElimina
  2. This was a shocking post. It has some look at here fundamental data on this subject. stainless fittings pipe supplier

    RispondiElimina
  3. I am happy to find your distinguished way of writing the post. Now you make it easy for me to understand and implement the concept. Thank you for the post. Almond Fall Nails

    RispondiElimina
  4. Exactly what I was searching for, regards for posting . eplus4car

    RispondiElimina
  5. Reese Witherspoon have the most beautiful eyes among american actresses, i just can’t get enough of her beautiful eyes` bench craft company lawsuit

    RispondiElimina

Posta un commento